We are Nexans, we electrify the future..
Product Characteristics: HEAT-SHRINKABLE STRAIGHT JOINTS FOR LHV UNARMORED SINGLE CORE POLYMERIC CABLES WITH CU WIRE / TAPE SCREEN Up to 26/45 (52) kV. STANDARDS: Test IEC 60840. APPLICATION: 52GTS1 straight joint are designed for unarmored plastic or HEPR insulated cables with Cu wire screen. Technical characteristics NGS semi-conductive tape is used to fill the gaps, cover the connector. The screen cut on both sides are covered with stress grading mastic plates as well as the connector area. The joint body consists of a stress control tubing, an insulating, heavy wall tubing and finally heavy dual wall screened insulating tube. The outer sheath is restored with GT4 adhesive lined heavy wall tubing.
designed to seal and insulate cable connections, offering protection from moisture, environmental factors, and electrical stresses
Used for connecting and terminating medium and high voltage (MV-HV) cables to electrical equipment, such as transformers, switchgear, and motors
Typically used in equipment isolated with oil, gas or air. Their plug-in system enables installation in reduces spaces (Euromold)